[GB/Appareils_mesure/menuappareils/menu_appareils_alptec2400.htm]

The products > Measuring devices > Alptec Network Analyzers > Main technical specifications and functions

Main technical specifications

All the measurements and precisions are full compliant
with IEC 61000-4-30 class A !

Power supply 190-260 Vac
240 to 360 Vdc
Battery backup 30 min
Number of input channels 4 V (0 to 660 V) / 4 l (5A peak)
up to 8 V (0 to 660 V) / 8 l (5A peak)
Sampling frequency 10.2 KHz / channel

 Integration period

Under & overvoltage 20 ms sliding / 8th of period
Instantaneous rms measurements 200 ms
Statistical rms Measurements: min; max; standard deviation 3 s, 10 min, 1 h, 24 h, 7 days
40 class histogram 3 s for 24 h, 10 min for 7 days
Data storage 64 MB (up to 512 MB, option)
Communication interface USB, Ethernet, RS 232, RS 485. Modem, GSM
Time synchronisation GPS and 10 min pulse
Accuracy: < 0.1 %

Main functions

Parameters Specifications Programmables detection thresholds Fault characterisation
Rapid variations: under voltage and overvoltage Recording of waveform of voltage and current fault. YES Type of fault according to UNIPEDE classification
Slow voltage variations 10 min measurement, according to EN 50160 thresholds YES Date & time, Type, Max value (min), Duration
Harmonics and inter-harmonics According to CEI 61000-4-7 standard YES Date & Time, Rank, Phase, Max value, Duration
Total harmonics distorsion According to EN 50160 thresholds YES Date & Time, Duration, Maximum value
Unbalance According to EN 50160 thresholds YES Date & Time, Duration, Maximum value
Flicker According to IEC868 standard; EN 61000-4-15 YES Date & Time, Duration, Maximum value
Frequency variation Measurement 10 s, according to EN 50160 thresholds YES Date & Time, Duration, Max value (min)
Remote control 2 remote controls analysed according to the EN 61037 standard: 1992 YES Injection rate and raster decoding up to 2500 Hz

Memory capabilities

Memory area Histograms Statistical measurements (Avg, Min, Max, s)
24 hours 7 days Integ. time 1 hour 24 hours 7 days
64 MB 95 meas
3 months
55 meas
1 year
3611 meas
25 days
2238 meas
3 months
373 meas
1 year
118 meas
2 years
128 MB
(option)
           
256 MB
(option)
           

Quality data (EN50160) & Centralized remote controls

Memory area Remote control
(immediate)
Counters
(daily)
Events
(immediate)
TOTAL number of blocs
(Useful Memory Size)
64 MB (option) 5094 TC
3 months
728 counters
2 years
4250 events
Fn (Q)
490 Blocks of 128 KB
(064,225,280 octets)
128 MB (option)        
256 MB (option)        


Introduction
Presentation of ALPTEC 2400
Different models of instruments
Main technical specifications and functions
Cases - Communication Interfaces - Synchronization - Environment
Embedded Web site
Associated Winalp 2000 software
     Presentation
     Main functions

Copyright © 2002-2007 Alpes Technologies - All rights reserved