[GB/Appareils_mesure/menuappareils/menu_appareils_alptec2400.htm] 
|
The products
>
Measuring devices
> Alptec
Network Analyzers
> Main technical specifications and functions
Main technical specifications
|
All the
measurements and precisions are full compliant
with IEC 61000-4-30 class A ! |
Power
supply 190-260 Vac
240 to 360 Vdc |
Battery
backup 30 min |
| Number of input
channels |
4 V (0 to 660 V)
/ 4 l (5A peak)
up to 8 V (0 to 660 V) / 8 l (5A peak) |
| Sampling
frequency |
10.2
KHz / channel |
|
Integration period |
Under &
overvoltage |
20 ms sliding /
8th of period |
| Instantaneous
rms measurements |
200
ms |
| Statistical rms
Measurements: min; max; standard deviation |
3 s, 10 min, 1
h, 24 h, 7 days |
|
40 class histogram |
3
s for 24 h, 10 min for 7 days |
| Data storage |
64 MB (up to 512
MB, option) |
| Communication
interface |
USB, Ethernet, RS
232, RS 485. Modem, GSM |
| Time synchronisation |
GPS and 10 min
pulse |
| Accuracy: |
<
0.1 % |
|

Main functions
| Parameters |
Specifications |
Programmables
detection thresholds |
Fault characterisation |
| Rapid
variations: under voltage and overvoltage |
Recording of
waveform of voltage and current fault. |
YES |
Type of fault
according to UNIPEDE classification |
| Slow voltage
variations |
10 min
measurement, according to EN 50160 thresholds |
YES |
Date &
time, Type, Max value (min), Duration |
| Harmonics and
inter-harmonics |
According to CEI 61000-4-7
standard |
YES |
Date &
Time, Rank, Phase, Max value, Duration |
| Total harmonics
distorsion |
According to EN
50160 thresholds |
YES |
Date &
Time, Duration, Maximum value |
| Unbalance |
According to EN
50160 thresholds |
YES |
Date &
Time, Duration, Maximum value |
| Flicker |
According to IEC868
standard; EN 61000-4-15 |
YES |
Date &
Time, Duration, Maximum value |
| Frequency
variation |
Measurement 10
s, according to EN 50160 thresholds |
YES |
Date &
Time, Duration, Max value (min) |
| Remote control |
2 remote
controls analysed according to the EN 61037 standard:
1992 |
YES |
Injection rate
and raster decoding up to 2500 Hz |
Memory capabilities
|
Memory area |
Histograms |
Statistical measurements (Avg, Min, Max, s) |
|
24 hours |
7 days |
Integ. time |
1 hour |
24 hours |
7 days |
|
64 MB |
95 meas
3 months |
55 meas
1 year |
3611 meas
25 days |
2238 meas
3 months |
373 meas
1 year |
118 meas
2 years |
128 MB
(option) |
|
|
|
|
|
|
256 MB
(option) |
|
|
|
|
|
|
Quality data (EN50160) & Centralized remote controls
| Memory
area |
Remote control
(immediate) |
Counters
(daily) |
Events
(immediate) |
TOTAL number of blocs
(Useful Memory Size) |
| 64 MB
(option) |
5094 TC
3 months |
728 counters
2 years |
4250 events
Fn (Q) |
490 Blocks of 128 KB
(064,225,280 octets) |
| 128 MB
(option) |
|
|
|
|
| 256 MB
(option) |
|
|
|
|

Introduction
Presentation
of ALPTEC 2400
Different models of instruments
Main technical specifications and functions
Cases - Communication Interfaces - Synchronization - Environment
Embedded Web site
Associated Winalp 2000 software
Presentation
Main functions
|