|
The products
>
Measuring devices
> ALPTEC
> ALPTEC Power factor controller
> Technical characteristics
ALPTEC Power factor controller


I - GENERAL INFORMATION
DESCRIPTION
Digital microprocessor power factor controller
3 digit 7 segment LED display
4 key membrane keypad
TTL-RS232 serial interface for set-up and automatic testing via PC (Personal
Computer)
Internal temperature sensor
Advanced functions for capacitor current overload measurement, average weekly power factor,
maximum value logging
2 relays programmable as alarm and/or fan control
VERSIONS
ALPTEC3 3 steps,
96 x 96 mm housing
ALPTEC5 5 steps, 96 x 96 mm
housing
ALPTEC7 7 steps, 96 x 96 mm
housing
ALPTEC12 12 steps, 144 x 144 mm housing
INSTALLATION
Install the controller according to
wiring diagrams.
The CT (Current Transformer) must be connected to the free phase, i.e. not on
phases used to
supply the unit, as indicated in the wiring diagrams.
The controller automatically recognizes the CT current flow. In case of
co-generation systems,
disable this function (refer to advanced menu section) and connect the CT
correctly.
- The CT secondary must be earthed/grounded
This equipment must be installed by trained personnel, complying to current
standards, to avoid
damages or safety hazards.
CONNECTIONS CONTROL
At the first power up, the ALPTEC display views --- which means no parameter has been
programmed yet.
In these conditions, a manual test of the steps can be conducted to check the connections.
By pressing the
or
key, the steps are connected or disconnected.
WARNING!
During this phase, the step control is totally manual and the unit does not control the reconnection time to
consent the capacitor discharge.
NOTE: Products illustrated here in are subject to alterations and changes without prior notice. Technical
data and descriptions in the documentation are accurate to the best of our knowledge, but no liabilities
for errors, omissions, or contingencies will be accepted.
FRONT PANEL DESCRIPTION
The display shows the
cos φ of the system together with the IND and CAP LEDs. The flashing decimal
point indicates the negative sign (inverse energy flow).
By pressing the MODE key, the V, A,
kvar, etc. LEDs are switched on one after another and the
relative measurement of each is viewed.
An optional function is available for each LED and indicated on front viewable by pressing the
key; the LED flashes quickly
thereafter.
For some measurements, a second optional function is displayable by pressing the
key.
Programmed: the
and
keys respectively increase or decrease the value. The set cos φ can be
adjusted between 0.80 IND and 0.80 CAP.
II - WAYS TO SET UP THE CONTROLLER
MANUAL KEYPAD SET-UP
For a manual set up it is necessary to set the proper value such as described in the parameter table.
Place the unit in manual mode and press the MODE key for 5 consecutive seconds (fig.1).
The word Set is viewed on the display to confirm access to the basic menu parameters (fig. 2).

| PARAMETER |
DESCRIPTION |
RANGE |
DEFAULT
SETTING |
| P.01 |
CT primary
current For values higher than 1000, a flashing dot indicates
"thousands" |
OFF to 10.00 |
OFF |
| P.02 |
Smallest step
kvar Rated power in kvar of the smallest installed capacitor
bank.
Example: for 10Kvar, set 10.0 |
0.10 to 300 |
1.00 |
| P.03 |
Rated capacitro
voltage. Rated voltage (nameplate) of the capacitors.
Example: for 440V, set 440 |
80 to 750V |
400 |
| P.04 |
Reconnection
time. Minimum time needed for the capacitor to discharge and
be ready to bu used again.
Example: for 60 seconds, set 060 |
5 to 240 sec. |
60 |
| P.05 |
Sensitivity. The
sensitivity is a coefficient, which adjust the controller
regulation speed. |
5 to 600 sec. |
30 |
| P.06 |
LED 1...n step coefficients
The coefficients of the steps represent the power of each step
in relation to the smallest capacitor bank, which value is
programmed at P.02 |
0 to 16 |
0 |
P.06
LED1 to LED n |
If a step has the same power rating of the smallest step, then its
coefficient will be 1, while if it is double it will be 2 and so on up to
a maximum of 16. By setting 0, the step will be disabled and will
never be considered or used by the controller. |
P.06
EXAMPLE |
With a ALPTEC7 installed in a control
panel with 6 capacitor banks, respectively 5, 10, 20, 20, 20, 20
kvar at rated 440V and needing to use the last step as alarm:
P.02 = 5.00 (smallest step=5Kvar)
P.03 = 440 (Rated voltage 440V)
P.06 LED1 = 001 (5kvar = 1 times P.02)
P.06 LED2 = 002 (10kvar = 2 times P.02)
P.06 LED3 = 004 (20kvar = 4 times P.02)
P.06 LED4 = 004 (20kvar = 4 times P.02)
P.06 LED5 = 004 (20kvar = 4 times P.02)
P.06 LED6 = 004 (20kvar = 4 times P.02)
P.06 LED7 = noR (Normally open alarm) |
NOTE:
The last two steps can be programmed to operate as normal steps or as alarm
relay or again as fan control.
If the second last step is linked to a function then the last step cannot be
used as a normal step.
To select these functions, press
until the following codes are viewed:
noR : Normally open alarm (contact open in absence of alarm)
ncR : Normally closed alarm (contact closed in
absence of alarm)
FAn : Fan control |
QUICK SET-UP VIA PC
For quick set-up via PC, it is necessary to use the relative automatic test and
remote control software ALPTECSW, that includes the PC software and the
connection cable (code 51 C11). For this reason, all the ALPTEC models are provided with a communication port in the
rear.
All of the parameters are viewed on the PC monitor. The settings can be transmitted and stored with
a few simple clicks of the mouse.
This solution is ideal if you have several controllers to programme with the same setting. The set-up
can be downloaded to a file and used to program other controllers.
When the capacitor bank is power up you can monitor any parameter such as
temperature, nominal voltage and current or the reactive power of each step can be viewed
AUTOMATIC SET-UP
The automatic set-up of parameters provides for the unit to be set working
without programming any parameter.
To activate the automatic set-up when the unit is in MAN or
--- mode, simultaneously press MODE and MAN/AUT keys for 5 seconds (fig. 1).
The wording ASE (Automatic Set-up) flashes indicating the automatic set-up of the parameters, is in
progress (fig. 2).

The procedure will last a few minutes during which the controller measures the power rating of the
connected steps. This measurement will then be continuously updated during the normal
operation.
If the load of the system varies frequently, the same step may have to be measured several times. In
this case, the procedure may last longer.
At the end of the automatic set-up, the controller is ready for automatic operation.
Important!
All of the relays are considered as normal capacitors banks. So no alarm relay or fan control
configuration is possible.
The capacitors installed must be with a power ratings multiple of 1, 2, 4, 8 or 16 times the smallest
capacitor step.
The unused steps must be positioned at the higher step
numbers.
Note:
After the automatic set-up is terminated, by manually changing the setting of
parameters, the controller will implement all the parameter programming. Therefore,
all of the measurements and functions will be available once again.
III - OPERATING MODE
The AUT and MAN LEDs indicate the automatic or manual operating mode.
To change mode, press the MAN/AUT key for at least 1 second.
When the SET COS φ LED is switched on, no mode change is possible.
The operating mode remains stored even if power is removed.
AUTOMATIC OPERATION
In automatic mode, the controller calculates the optimum configuration to achieve the set
cos φ value.
The selection criteria take into consideration many variables such as: power of each step, the number
of operations, the total time of usage, reconnection time, etc.
The controller displays the imminent connection or disconnection of the step by the AUT LED
flashing. The LED flashing can last in cases when the connection of a
step is not possible because of the reconnection time (i.e. capacitor discharge time).
MANUAL OPERATION
When the controller is in manual mode, one of the steps can be selected and manually connected or
disconnected.
If a measurement other than
cos φ is viewed, press MODE until all the LEDs of the measurements
are switched off.
To select one of the steps, use the
and
keys. The LED of the selected step starts flashing quickly.
Press MODE to connect or disconnect the selected step.
If the reconnection time of the selected step has not elapsed, the MAN LED
flashes to indicate the operation has been confirmed and will be conducted in due
time.
The manual configuration of the steps is maintained even when voltage is
removed. When power returns, the original state of the steps is
restored.
KEYPAD LOCK
A function to exclude all modification to operating parameters can be enabled; measurement viewing
is still provided in any case.
To lock and unlock the keypad, push and keep MODE key pressed. Then press the
key three times and the
key twice and then release MODE. The display will view LOC when the keypad is locked and
UnL when unlocked.
When the lock is enabled, it is not possible to make the following
operations:
By attempting to conduct the above operations, the display will view LOC to indicate the locked
keypad state.
IV - ALARMS
When the controller detects an abnormal situation in the system, a flashing alarm code
is displayed. By pressing any key, the alarm viewing will be momentarily ignored to
permit the user to check all the measurements. If no key is pushed for 30
seconds and the alarm conditions persist, the alarm code will be displayed once
again.
Each alarm can cause diverse results such as the alarm relay tripping, the delayed or
immediate step disconnection, etc., according to the programmed
property.
The property of each alarm can be changed (e.g. disabled, change the delay time or
effect), by using a PC and the relative software (order code ALPTEC SW), used for the
quick parameter set-up.
The following table indicates the alarm codes and the relative meaning of each along
with the default setting.
ALARM
CODE |
DESCRIPTION |
ENABLING |
ALARM
RELAY |
DISCON-
NECTION |
TRIPPING
DELAY |
| A01 |
Under compensation:
Capacitor are all connected and cos φ is lower than
set point value. |
Y |
Y |
N |
015
min |
| A02 |
Over
compensation:
All capacitors are disconnected and cos φ is higher
than set point value. |
Y |
N |
N |
120
s |
| A03 |
Low
current:
Current value is lower than 2.5% full scale value. In
automatic, the capacitors are disconnected after 2 minutes. |
Y |
N |
N |
5
s |
| A04 |
High
current:
Current value is 120% higher than full scale value. |
Y |
N |
N |
120
s |
| A05 |
Low
voltage:
Voltage value is -15% lower than lower rate voltage. |
Y |
Y |
Y |
5
s |
| A06 |
High
voltage:
Voltage value is +10% higher than rated voltage. |
Y |
N |
Y |
5
min |
| A07 |
Capacitor
overload:
Current value flowing in the capacitors is higher than the
set threshold (refer to P20 and P21). |
Y |
Y |
Y |
120
s |
| A08 |
Over temperature:
Internal temperature is higher than setted threshold (refer
P27). |
Y |
Y |
Y |
30
s |
| A09 |
No-voltage
release:
Voltage failure |
Y |
N |
N |
0
s |
|