The products > Measuring devices > Current transformers > Technical guide

Current transformers

Description
Choice of transformers
Technical guide

Rated Burden for current circuit

Maximun demand ammeter 2,8 VA
Moving-iron ammeter 1,1 VA
Moving-coil ammeter with retifier < 1 VA
Wattmeter - Varmeter 0,5 VA
Power factor meter 0,5 VA
KWh meters 0,5 VA
Digital ammeter < 1 VA

VA per meter of twin cable at 20° C*

Section Cuivre
mm2
Secondaire 5A
VA
Secondaire 1A
VA
1 1,00 0,04
1,5 0,68 0,028
2,5 0,41 0,016
4 0,26 0,01
6 0,17 0,007
10 0,098 0,007
16 0,062 0,0025

* For each 10°C of temperature variation, VA absorbed by cable increase by 4%.