ALPISTATIC composition and characteristics

ALPISTATIC includes:

  • a capacitor bank split into several steps depending on the compensator power rating

  • one three-pole solid state contactor per step (cutting all three phases)

  • fan-cooled heat sink on each solid state contactor

  • standard type and duty type: 3 single phase damping reactors providing protection of the solid state contactor

  • SAH type: 1 anti-harmonic reactor, three phase, providing protection of the solid state contactor and protection from harmonics

  • one set of three HRC fuses per step

  • a control system for the solid state contactors, including:

    • a reactive energy controller for automatic control

      • with automatic / manual operation

      • front panel display showing the number of stages operating

      • front panel display of cos φ

      • front panel display of many other electrical parameters (harmonics, etc.)

    • microprocessor instrumentation and control board using solid state contactors:

      • triggers and releases contactors within 40 milliseconds max.

      • avoids any transient voltages and currents when steps are triggered or released.

GENERAL CHARACTERISTICS

  • IP 315 cabinet

  • protection of parts under power against direct contact: IP 2X

  • temperature class

    • operation: -10 / +45°C (average over 24 hours: 40°C)

    • storage: -30 / +60°C

  • ventilation: forced

  • color:

    • grey cabinet (RAL 7032),

    • black base

  • cables enter at the bottom (at the top on request)

  • standards: 

    • EN 60439-1,

    • IEC 60439-1 and 2

ELECTRICAL CHARACTERISTICS

  • Insulation class: 0.66 kV (tested at 2.5 kV, 50 Hz for one minute)

  • built-in power supply for auxiliary circuits

  • built-in connection terminal block for brown-out contact

OPTIONS

  • protection circuit breaker

  • fixed step

  • adder-type current transformer

CONNECTIONS

Allow for: 

  • power cables as per table on page 28

  • current transformer to be located on phase L1 of the facility, upline from all receivers and the capacitor bank.

    • primary: rating depending on installation

    • secondary: 5 A (1 A on request)

    • power: 10 VA (recommended) – class 1

  • note: this transformer can be supplied separately on request.