The products > Reactive energy compensation > Low voltage capacitors and capacitor banks > Protective circuit breaker and connection cable selection table for capacitors

Three-phase 400 V and 440 V capacitor Nominal power (kvar) Three-phase circuit breaker
Rating/Thermal setting (A)
Cables
minimum cross-section
per phase
Cu (mm2) Al (mm2)
10 20/20 6 10
20 40/40 10 16
30 63/60 16 25
40 80/80 25 35
50 100/100 35 50
60 125/125 35 50
70 160/140 35 50
80 160/160 50 70
90 200/180 50 70
100 200/200 70 95
125 250/250 70 95
150 400/300 95 120
175 400/350 120 185
200 400/400 150 240
225 630/450 150 240
250 630/500 185 2 x 120
275 630/550 185 2 x 120
300 630/600 2 x 95 2 x 150
325 630/630 2 x 95 2 x 150
350 800/700 2 x 120 2 x 185
375 800/750 2 x 120 2 x 185
400 800/800 2 x 150 2 x 240
450 1000/900 2 x 150 2 x 240
500 1000/1000 2 x 185 4 x 150
550 1250/1100 2 x 185 4 x 150
600 1250/1200 4 x 120 4 x 185
650 1250/1250 4 x 120 4 x 185
700 1600/1400 4 x 150 4 x 240
750 1600/1500 4 x 150 4 x 240
800 1600/1600 4 x 150 4 x 240
850 2000/1700 4 x 150 4 x 240
900 2000/1800 4 x 150 4 x 240
950 2000/1900 4 x 185 4 x 300
1000 2000/2000 4 x 185 4 x 300

NOTE: The cable cross-section indicated in this table is the minimum recommended section. It does not take into account additional correcting factors (fitting method, temperature, long distances, etc.). The calculations are for unipolar cables mounted in ambient air at 30°C.