The products
> Reactive energy compensation > Low
voltage capacitors and capacitor banks >
Protective circuit breaker and connection cable selection table for
capacitors
| Three-phase 400 V
and 440 V capacitor Nominal power (kvar) |
Three-phase
circuit breaker
Rating/Thermal setting (A) |
Cables
minimum cross-section
per phase |
| Cu (mm2) |
Al (mm2) |
| 10 |
20/20 |
6 |
10 |
| 20 |
40/40 |
10 |
16 |
| 30 |
63/60 |
16 |
25 |
| 40 |
80/80 |
25 |
35 |
| 50 |
100/100 |
35 |
50 |
| 60 |
125/125 |
35 |
50 |
| 70 |
160/140 |
35 |
50 |
| 80 |
160/160 |
50 |
70 |
| 90 |
200/180 |
50 |
70 |
| 100 |
200/200 |
70 |
95 |
| 125 |
250/250 |
70 |
95 |
| 150 |
400/300 |
95 |
120 |
| 175 |
400/350 |
120 |
185 |
| 200 |
400/400 |
150 |
240 |
| 225 |
630/450 |
150 |
240 |
| 250 |
630/500 |
185 |
2 x 120 |
| 275 |
630/550 |
185 |
2 x 120 |
| 300 |
630/600 |
2 x 95 |
2 x 150 |
| 325 |
630/630 |
2 x 95 |
2 x 150 |
| 350 |
800/700 |
2 x 120 |
2 x 185 |
| 375 |
800/750 |
2 x 120 |
2 x 185 |
| 400 |
800/800 |
2 x 150 |
2 x 240 |
| 450 |
1000/900 |
2 x 150 |
2 x 240 |
| 500 |
1000/1000 |
2 x 185 |
4 x 150 |
| 550 |
1250/1100 |
2 x 185 |
4 x 150 |
| 600 |
1250/1200 |
4 x 120 |
4 x 185 |
| 650 |
1250/1250 |
4 x 120 |
4 x 185 |
| 700 |
1600/1400 |
4 x 150 |
4 x 240 |
| 750 |
1600/1500 |
4 x 150 |
4 x 240 |
| 800 |
1600/1600 |
4 x 150 |
4 x 240 |
| 850 |
2000/1700 |
4 x 150 |
4 x 240 |
| 900 |
2000/1800 |
4 x 150 |
4 x 240 |
| 950 |
2000/1900 |
4 x 185 |
4 x 300 |
| 1000 |
2000/2000 |
4 x 185 |
4 x 300 |
NOTE: The cable cross-section indicated in this table is the minimum recommended section. It does not take into account
additional correcting factors (fitting method, temperature, long distances, etc.). The calculations are for unipolar
cables mounted in ambient air at 30°C.