The products
> Reactive energy compensation
> High voltage capacitors
and capacitor banks > High
voltage capacitor banks > Additional
accessories
Quick discharge reactors
Installing two quick discharge reactors or potential
transformers between the phases of the bank makes it possible to reduce the capacitor discharge time from
10 minutes to approximately 10 seconds.
This reduction in the discharge time :
-
provides safety for personnel during any interventions
-
reduces the waiting period before ground (closing of
MALT isolating switch)
-
makes it possible to reactivate the banks in steps
more quickly after a power cut, although a min. time of 5 minutes is essential between two
discharges, in order to ensure correct cooling of the discharge reactors.
Damping reactors
Installing damping reactors in series on each phase of
the bank makes it possible to reduce surge currents to acceptable values for the corresponding control device.
These are necessary in the following cases :
High
voltage summary
|