The products > Reactive energy compensation > General information > How to calculate the power of capacitors

1 - CALCULATION FROM ELECTRICITY BILLS (LV or MV metering EDF "Tarif Vert" rate subscribers)

THIS WAY OF CALCULATION MATCH
THE FRENCH REACTIVE ENERGY INVOICE SYSTEM.
THEN, EACH COUNTRY MUST USE ITS OWN SYSTEM FOR THE CALCULATION.

From 1st November 1987, in France, the reactive energy billing limit changed for all "tarif Vert" rate subscribers (LV or MV metering) to:
* tg φ = 0.4 or cos = 0.928: on the primary winding,
* tg φ = 0.31 or cos = 0.955: on the secondary winding.

For the calculation of the capacitor banks to be installed, proceed using the following method:

  • analyze the 5 electricity bills from November to March,

  • select the month for which the bill is the highest (kvarh to be billed),

  • evaluate the number of hours of operation of the installation every month in day-tariff and peak hours (generally 6 a.m. to 10 p.m. excluding Sundays),

  • calculate the capacitor power Qc to be installed

Qc =

kvarh to be billed (monthly)


Nb. of working hours (monthly)

* for LV metering, in the calculation of the kvarh to be billed, EDF introduces a fixed rate transformer consumption by applying a coefficient of 0.09 on the secondary winding tg φ calculated to obtain the primary winding tg φ.

Example
Take the subscriber SMITH:
. highest reactive energy bill: December 87,
. number of kvarh to be billed: 70,000,
. monthly number of hours of operation: 350 hours (day-tariff + peak)

Qc (bank to be installed) =

70 000

 = 200 kvar


350

 

2 - CALCULATION FROM MEASURING ELEMENTS REAS ON THE HV/LV TRANSFORMER SECONDARY WINDING/ PkW - COS φ

Example
Take a plant powered from an 800 kVA HV / LV subscriber statio which would like to change the power factor of its installation to:
* Cos φ = 0.928 (tg φ = 0.4) on the primary winding
* or Cos φ = 0.955 (tg φ = 0.31) on the secondary winding
with the following readings:

• voltage: 400 V three-phase 50 HZ
• P = 475
• Cos (secondary) = 0.75 (or tg φ = 0.88)

Qc (bank to be installed) = Pkw (tg φ measured - tg φ to obtained)

Qc = 475 (0.88 - 0.31) # 270 kvar

Note: the coefficient K = (tg φ measured - tg φ to be obtained) is obtained easily from the Cos φ values using the conversion table.

 

3 - CALCULATION FOR FUTURE INSTALLATIONS

For future installations, compensation is frequently requested from the commissioning stage. In this case, it is impossible to calculate the bank using conventional methods (electricity bill or measurements on-site).
For this type of installation, it is recommended to install a capacitor bank equal to approximately 25% of the nominal power of the corresponding HV / LV transformer.

Example

1000 kVA transformer =>  Q capacitor = 250 kvar

Note : this type of ratio corresponds to the following operating conditions:

• 1000 kva transformer

• real transformer load = 75%

• Cos φ of load = 0.80

}

 k = 0.421 (table)

• Cos φ to be obtained = 0.95

Qc = 1000 x 75 % x 0.80 x 0.421 = 250 kvar

  

4 - CALCULATION FOR INDEPENDENT PRODUCERS (SMALL POWER STATIONS)

For this type of installation, the independent producer must supply the electricity company with a quantity of reactive energy equal to at least 40% of its active energy production during WINTER day-tariff and peak hours.
In this case, the calculation of the capacitor bank should account for:

• the on-load reactive consumption of the generator
• the on-load consumption of the LV / HV transformer (if applicable)
• the reactive energy to be supplied, or 40% of the active energy produced

General information summary

Copyright © 2002-2007 Alpes Technologies - All rights reserved
Realization
Media Welcome